7. PARAMETER SETTING VM-5S
-30-
7-4 PARAMETER SETTING 1
7-4-1 PARAMETER SETTING 1
Setting the parameters for OK alarm / SPEED RELAY reset mode, OK alarm /
SPEED RELAY delay time, OK alarm / SPEED RELAY mode, first-out display, timed
OK channel defeat and peak hold is enabled.
Setting the address for use in combination with the VM-5H3 or VM-5W1 Instrument
Rack and VM-5P1,2 Communication/Phase Marker Unit or VM-53 Dual
Communication Unit is enabled.
7-4-2 MODE SELECT SWITCH SETTING
1)1BY(CH1 BYPASS) S.W.
2)2BY(CH2 BYPASS) S.W.
3) DBY(DANGER BYPASS) S.W.
4) MS1(MODE-SELECT1) S.W. (normally OFF)
5) MS2(MODE-SELECT2) S.W.
6) N·A(not available)
DIP switches
Confirm that the MS1 (MODE-SELECT1) switch is "OFF".
Place the MS2 (MODE-SELECT2) switch in "ON" position.
Setting other than the above are not enabled to set the parameters.
OFF
ON
1 2 3 4 5 6