Issue 01/05 Attachment
CANopen Option Module Operating Instructions
6SE6400-5BC00-0BP0
123
8 Attachment
8.1 Technical data
Table 8-1 Technical data
Order No. 6SE6400-1CB00-0AA0
Size
(Height x Width x Depth)
161 mm x 73 mm x 43.5 mm
Degree of pollution Degree of pollution 2 according to IEC 60 664-1 (DIN VDE
0110/T1),
moisture condensation during operation is not permissible
Mechanical strength
Stationary
- deflection
- acceleration
During transport
- deflection
- acceleration
Acc. to DIN IEC 60 068-2-6 (with a correctly installed module)
0.15 mm frequency range between 10 Hz and 58 Hz
19.6 m/s
2
frequency range from > 58 Hz to 500 Hz
3.5 mm frequency range between 5 Hz and 9 Hz
9.8 m/s
2
frequency range from > 9 Hz to 500 Hz
Climatic Class (in
operation)
Class 3K3 according to DIN IEC 60 721-3-3
Cooling type Air self-cooling
Permissible ambient or
cooling-medium
temperature
- operation
- storage
- transport
–10 °C to +50 °C (14 °F to 122 °F)
–40 °C to +70 °C (–40 °F to 158 °F)
–25 °C to +70 °C (–13 °F to 158 °F)
Relative air humidity
(perm. humidity class)
In operation
During transport and
storage
<= 85 % rF (moisture condensation not permissible)
<= 95 % rF
Power supply Power is supplied to the CAN bus from the MICROMASTER's
power supply
Output voltage None
Data transfer rate 10, 20, 50, 125, 250, 500, 800 kbaud and 1Mbaud