13/30
Siemens Climatix touch
panel A6V10445442_en--_a
Building Technologies Mounting and connecting 2015-06-30
4. Mounting and connecting
4.1 Preparations
Check the package content for visible signs of transport damage and for
completeness.
Do not install parts damaged during shipment. Contact your Siemens
representative in the event of damaged parts.
Note the information in the following sections of these operating instructions before
installing the Climatix touch panel:
- Climatic ambient conditions
- Protection classes
The following clearances are required around the Climatix touch panel to ensure
sufficient self-ventilation:
x y1 y2 z
POL8T1.4X/STD
POL8T1.7X/STD
POL8T1.8X/STD
10
10
10
10
10
10
75 25
50 20
50 20
Unit of measurement: mm
Avoid mounting the Climatix touch panel near other devicesā AC power cable,
controller output module, relay, or other electrical equipment.
Keep the Climatix touch panel away from equipment such as frequency converters
and power supply units, and shields all input or output cables to the equipment.
The shielding must be properly earth grounded.
Dimensions of the mounting cutout for the Climatix touch panel:
w
h
POL8T1.4X/STD
POL8T1.7X/STD
POL8T1.8X/STD
163 mm
210 mm
330 mm
85 mm
144 mm
246 mm
operating