Commissioning
4.10 Switching off air-cooled motors
A5E01083943A AB
66 Siemens AG Operating Instructions 2.02 1FW4
4.10 Switching off air-cooled motors
Measures during de-energizing
If the corresponding control action does not take place automatically, switch on the anti-
condensation heating if present. You must not switch on the anti-condensation heating until
at least one hour after the motor has been switched off. This prevents damage to the winding
insulation. [ID 618.02]