EasyManuals Logo
Home>Siemens>Media Converter>MIDIMASTER Vector

Siemens MIDIMASTER Vector User Manual

Siemens MIDIMASTER Vector
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
G85139-H1751-U529-D1 © Siemens plc 199
9
4/8/99
4
Safety Instructions
Before installing and putting this equipment into operation, please read these safety instructions and warnings carefully and
all the warning signs attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace
missing or damaged labels.
WARNING
This equipment contains dangerous voltages and control
s
dangerous rotating mechanical parts. Loss of life, sever
e
personal injury or property damage can result if the instruction
s
contained in this manual are not followed.
Only suitable qualified personnel should work on this equipment
,
and only after becoming familiar with all safety notices
,
installation, operation and maintenance procedures contained i
n
this manual. The successful and safe operation of this equipmen
t
is dependent upon its proper handling, installation, operation an
d
maintenance.
· The MICROMASTER and MIDIMASTER Vector unit
s
operate at high voltages.
· Only permanently-wired input power connections ar
e
allowed. This equipment must be grounded (IEC 536 Clas
s
1, NEC and other applicable standards).
· If a Residual Current-operated protective Device (RCD) is t
o
be used it must be an RCD type B.
· The dc-link capacitor remains charged to dangerou
s
voltages even when the power is removed. For this reason i
t
is not permissible to open the equipment until five minute
s
after the power has been turned off. When handling th
e
open equipment it should be noted that live parts ar
e
exposed. Do not touch these live parts.
· Machines with a three phase power supply, fitted with EM
C
filters, must not be connected to a supply via an ELC
B
(Earth Leakage Circuit-Breaker - see DIN VDE 0160, sectio
n
6.5).
· The following terminals can carry dangerous voltages even i
f
the inverter is inoperative:
- the power supply terminals L/L1, N/L2 and L3 (MMV) - L1,
L2, and L3 (MDV).
-the motor terminals U, V, W.
-the braking resistor terminals B+/DC+ and B-(MMV).
-the braking unit terminals DC+ and DC- (MDV).
· Only qualified personnel may connect, start the system u
p
and repair faults. These personnel must be thoroughl
y
acquainted with all the warnings and operating procedure
s
contained in this manual.
· Certain parameter settings may cause the inverter to restar
t
automatically after an input power failure.
· This equipment is capable of providing internal moto
r
overload protection in accordance with UL508C section 42
.
Refer to P074. Motor overload protection can also b
e
provided by using an external PTC.
This equipment is suitable for use in a circuit capable o
f
delivering not more than 100,000 symmetrical ampere
s
(rms), for a maximum voltage of 230/460V* when protecte
d
by a time delay fuse*.
*As detailed in section 8.
· This equipment must not be used as an ‘emergency stop
mechanism (see EN 60204, 9.2.5.4).
CAUTION
· Children and the general public must be prevented fro
m
accessing or approaching the equipment!
· This equipment must only be used for the purpose specifie
d
by the manufacturer. Unauthorised modifications and the us
e
of spare parts and accessories that are not sold o
r
recommended by the manufacturer of the equipment ca
n
cause fires, electric shocks and injuries.
· Keep these operating instructions within easy reach and giv
e
them to all users!
European Low Voltage Directive
The MICROMASTER Vector and MIDIMASTER Vector product range
complies with the requirements of the Low Voltage Directive 73/23/EEC as
amended by Directive 93/68/EEC. The units are certified for compliance with
the following standards:
EN 60146-1-1 Semiconductor converters - General requirements and
line commutated converters
EN 60204-1 Safety of machinery - Electrical equipment of machines
European Machinery Directive
The MICROMASTER Vector and MIDIMASTER Vector inverter series do not fall
under the scope of the Machinery Directive. However, the products have been
fully evaluated for compliance with the essential Health & Safety requirements of
the directive when used in a typical machine application. A Declaration of
Incorporation is available on request.
European EMC Directive
When installed according to the recommendations described in this manual,
the MICROMASTER Vector and MIDIMASTER Vector fulfil all requirements
of the EMC Directive as defined by the EMC Product Standard for Power
Drive Systems EN61800-3.
Underwriters Laboratories
ISO 9001
Siemens plc operates a quality management system, which complies with
the requirements of ISO 9001.
UL and CUL listed power
conversion equipment 5B33 for
use in a pollution degree 2
environment

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MIDIMASTER Vector and is the answer not in the manual?

Siemens MIDIMASTER Vector Specifications

General IconGeneral
BrandSiemens
ModelMIDIMASTER Vector
CategoryMedia Converter
LanguageEnglish

Related product manuals