8. SPECIFICATIONS English
© Siemens plc 1999 G85139-H1751-U529-D1
65
4/8/9
8. SPECIFICATIONS
230V Single Phase MICROMASTER Vector Inverters
Order No.(with built-in filter class A (6SE32)).
10-7BA40 11-5BA40 12-1BA40 12-8BA40 13-6BA40 15-2BB40 16-8BB40 21-0BC40 21-3BC40
Inverter model MMV12 MMV25 MMV37 MMV55 MMV75 MMV110 MMV150 MMV220
MMV300
c
Input voltage range 1 AC 208V - 240 V +/-10%
Motor output rating
a
(kW/hp)
0.12/
1
/
6
0.25/
1
/
3
0.37/½ 0.55/¾ 0.75/ 1 1.1 / 1½ 1.5 / 2 2.2 / 3 3.0/ 4
Continuous output @ 230V 350VA 660 VA 880 VA 1.14 kVA 1.5 kVA 2.1 kVA 2.8 kVA 4.0 kVA 5.2kVA
Output current (nom.) (A)
a
0.75 1.5 2.1 2.6 3.5 4.8 6.6 9.0 11.8
Output current (max. continuous) (A) 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Input current (max.) (A) 1.8 3.2 4.6 6.2 8.2 11.0 14.4 20.2 28.3
Recommended mains fuse(A) 10 16 20 25 30
Fuse order code 3NA3803 3NA3805 3NA3807 3NA3810 3NA3814
Recommended lead Input 1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output 1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d) 73 x 175 x 141 149 x 184 x 172 185 x 215 x 195
Weight (kg / lb) 0.85 / 1.9 2.6 / 5.7 5.0 / 11.0
All 1 AC 230 V MICROMASTER Vector include integrated Class A filters. Optional external Class B filters are available (see section 9.3).
230 V 1/3 AC MICROMASTER Vector Inverters
Order No. (6SE32..)
10-7CA40 11-5CA40 12-1CA40 12-8CA40 13-6CA40 15-2CB40 16-8CB40 21-0CC40 21-3CC40 21-8CC40
Inverter model MMV12/2 MMV25/2 MMV37/2 MMV55/2 MMV75/2 MMV110/2 MMV150/2 MMV220/2 MMV300/2
c
MMV400/2
Input voltage range 1 - 3 AC 208V - 240 V +/-10% 3 AC
Motor output rating
a
(kW/hp)
0.12/
1
/
6
0.25/
1
/
3
0.37/½ 0.55/¾ 0.75/ 1 1.1 / 1½ 1.5 / 2 2.2 /3 3.0 / 4 4.0 /5
Continuous output @ 230V 480VA 660 VA 880 VA 1.14 kVA 1.5 kVA 2.1 kVA 2.8 kVA 4.0 kVA 5.2 kVA 7.0kVA
Output current (nom.) (A)
a
0.8 1.5 2.1 2.6 3.5 4.8 6.6 9.0 11.8 15.9
Output current (max. continuous) (A) 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6 17.5
Input current (I rms) (1 AC / 3
AC)
1.8/1.1A 3.2/1.9A 4.6/2.7A 6.2/3.6A 8.2/4.7A 11.0/6.4
A
14.4/8.3
A
20.2/11.7A 28.3/16.3
A
-/21.1 A
Recommended mains fuse(A)
b
10 16 20 25 30 25
Fuse order code 3NA3803 3NA3805 3NA3807 3NA3810 3NA3814 3NA3810
Recommended lead Input 1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output 1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d) 73 x 175 x 141 149 x 184 x 172 185 x 215 x 195
Weight (kg / lb) 0.75 / 1.7 2.4 / 5.3 4.8 / 10.5
All 1 AC and 3 AC 230 V MICROMASTERS (excluding MMV400/2) are suitable for 208 V operation.
All 3 AC 230 V MICROMASTER Vector can operate on 1 AC 230 V (MMV300/2 requires an external line choke, e.g. 4EM6100-3CB).
380 V - 500 V Three Phase MICROMASTER Vector Inverters
Order No. (6SE32..)
11-1DA40 11-4DA40 12-0DA40 12-7DA40 14-0DA40 15-8DB40 17-3DB40 21-0DC40 21-3DC40 21-5DC40
Inverter model MMV37/3 MMV55/3 MMV75/3 MMV110/3 MMV150/3 MMV220/3 MMV300/3 MMV400/3 MMV550/3 MMV750/3
Input voltage range 3 AC 380 V - 500 V +/-10%
Motor output rating
a
(kW/ hp)
0.37 /½ 0.55 / ¾ 0.75 / 1 1.1 /1½ 1.5 / 2 2.2 / 3 3.0 / 4 4.0 / 5 5.5 / 7½ 7.5 / 10
Continuous output @ 400V
a
930VA 1180VA 1530VA 2150VA 2.8 kVA 4.0 kVA 5.2 kVA 7.0 kVA 9.0 kVA 12.1 kVA
Output current (nom.) (A) 1.2 1.5 2.0 2.8 3.7 5.2 6.8 9.2 11.8 15.8
Output current (max. continuous) (A)* 1.2 1.6 2.1 3.0 4.0 5.9 7.7 10.2 13.2 17.5
Input current (max.) (A) 2.2 2.8 3.7 4.9 5.9 8.8 11.1 13.6 17.1 22.1
Recommended mains fuse(A) 10 16 20 25
Fuse order code 3NA3803 3NA3805 3NA3807 3NA3810
Recommended lead Input 1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output 1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d) 73 x 175 x 141 149 x 184 x 172 185 x 215 x 195
Weight (kg / lb) 0.75 / 1.7 2.4 / 5.3 4.8 / 10.5
Optional external Class A and Class B filters are available (see section 9.3).
.
Notes:
a
Siemens 4 pole-motor, 1LA5 series or equivalent.
b
Assumes 3-phase supply. If a single phase supply is used, the input current ratings, wire sizes and fuses for single phase
MICROMASTERS will apply.
c
MMV300 and MMV300/2 require an external choke (e.g. 4EM6100-3CB) and a 30 A mains fuse to operate on a single phase supply.
* Output current ratings are reduced by 10% when operating on mains supply voltages over 460V.