RUGGEDCOM RX1500
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications 39
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
• Section 4.1, “Power Supply Specifications”
• Section 4.2, “Failsafe Relay Specifications”
• Section 4.3, “Copper Serial Port Specifications”
• Section 4.4, “Copper Ethernet Port Specifications”
• Section 4.5, “Fiber Optic Ethernet Port Specifications”
• Section 4.6, “Cellular Modem Specifications”
• Section 4.7, “Operating Environment”
• Section 4.8, “RUGGEDCOM APE Specifications”
• Section 4.9, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
Input Range
Power
Supply Type
Min Max
Internal
Fuse Rating
Maximum Power
Consumption
a
Maximum
Cable Length
b
Insulation
88 VDC 300 VDC
HI
85 VAC 264 VAC
3.15 A(T)
c
65 W —
88 VDC 300 VDC
HIP
85 VAC 264 VAC
3.15 A(T)
c
65 W —
2800 VDC
for 1 minute
24
24P
13 VDC 36 VDC 10 A(T)
c
63.5 W 9.4 m (30.8 ft)
48
48P
36 VDC 72 VDC 3.15 A(T)
c
60 W 45.5 m (149 ft)
1500 VDC
for 1 minute
12
12P
9 VDC 15 VDC 12 A 67 W 5.5 m (18 ft)
1500 VAC or
2121 VDC
for 1 minute
a
Power consumption varies based on the device configuration.
b
Based on #16 AWG wiring.
c
(T) denotes time-delay fuse.