Application and functions
1.4 Telecontrol communication of the CP 1542SP-1 IRC
CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1
Operating Instructions, 01/2017, C79000-G8976-C426-03
13
1.4
Telecontrol communication of the CP 1542SP-1 IRC
Telecontrol protocols
In addition to the communications services named above, the CP 1542SP-1 IRC supports
the following telecontrol protocols for communication with a master station:
TeleControl Basic
This is a proprietary protocol of Siemens for telecontrol applications. The IP-based
protocol is used to connect the CP to the application TCSB.
TCSB is installed on a PC in the master station, the telecontrol server. Via the OPC-DA or
OPC-UA server of TCSB, an OPC client can access the process data of the CP.
TCSb is supported as of the following version: V3.0 + SP3
For the TCSB manual, see /3/ (Page 120).
DNP3
The CP functions as a DNP3 station (Outstation).
Communication is based on the DNP3 SPECIFICATION Version 2.11 (2007/2009).
You will find a detailed overview of the attributes and properties specified in the DNP3
protocol and supported by the CP in the DNP3 device profile, see Link:
(https://support.industry.siemens.com/cs/ww/en/ps/22143/man).
You will find the supported object groups and variations in the section Datapoint types
(Page 59).
Communications partner (DNP3) can be:
SIMATIC PCS7 TeleControl
SIMATIC WinCC TeleControl
SIMATIC WinCC OA
A TIM module with DNP3 capability (TIM 3V IE DNP3 / TIM 4R IE DNP3)
For the manual of the TIM module see /5/ (Page 120).
Third-party systems that support the DNP3 specification named above.
IEC 60870-5-104
The CP functions as a substation (slave).
Communication is based on the specification IEC 60870-5 Part 104 (2006).
You will find a detailed overview of the attributes and properties specified in the IEC
specification and supported by the CP in the IEC device profile, see Link:
(https://support.industry.siemens.com/cs/ww/en/ps/22143/man).
You will find the supported IEC type identifiers as in the section Datapoint types
(Page 59).
Communications partner (IEC master) can be:
SIMATIC PCS7 TeleControl
SIMATIC WinCC TeleControl

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET ET 200SP and is the answer not in the manual?

Siemens SIMATIC NET ET 200SP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET ET 200SP
CategoryNetwork Router
LanguageEnglish

Related product manuals