Configuration and operation
4.5 Telecontrol communication (CP 1542SP-1 IRC)
CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1
52 Operating Instructions, 01/2017, C79000-G8976-C426-03
If you do not want to use both ports of the bus adapter, you can disable one of the two ports.
You will find information on the other parameters in the information system of STEP 7.
The STEP 7 configuration of the communications partners of the CP (telecontrol server,
DNP3 or IEC master) and the connections to the partners is not possible and not necessary.
Address information of the communications partners
For the communications partners of the CP, the following information is required during the
configuration of the CP:
● TeleControl Basic
– Partner IP address
See section Auto-Hotspot for information on this.
– Partner port (port number of the listener port of TCSB)
● DNP3 / IEC
– Master station address
Station address specified on the master
With the IEC protocol the Master station address is not evaluated.
– Partner IP address
IP address of the master
For the addressing of redundant partners, see section Addressing of single and
redundant communications partners (Page 55).
– Partner port
"Partner stations" (only with DNP3 / IEC)
●
CP's own listener port
"Telecontrol server" / "Partner"
●
Enable the option to be able to use the partners configured later for the communication.
In "TeleControl Basic" the telecontrol server is always enabled as a partner.