Configuration and operation
4.5 Telecontrol communication (CP 1542SP-1 IRC)
CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1
Operating Instructions, 01/2017, C79000-G8976-C426-03
61
Format (memory
requirements)
Data point type
DNP3 object group
[variations]
Direction
S7 data types
Operand area
Integer (32 bits)
Counter Static
20 [1]
in
UDInt, DWord
I, Q, M, DB
Frozen Counter
2)
21
[1, 5] in
Counter Event
22 [1, 5]
in
UDInt, DWord
I, Q, M, DB
Frozen Counter Event
3)
23 [1, 5]
in
Analog Input
30 [1]
in
DInt
Q, M, DB
Analog Input Event
32 [1]
in
DInt
Q, M, DB
Analog Output Status
4)
40 [1, 3]
out
Analog Output
41 [1]
out
DInt
Q, M, DB
Analog Output Event
4)
42 [1]
out
Floating-point number
(32 bits)
Analog Input
30 [5]
in
Real
Q, M, DB
Analog Input Event
32 [5, 7]
in
Real
Q, M, DB
Analog Output Status
4)
40 [3]
out
Analog Output
41 [3]
out
Real
Q, M, DB
Analog Output Event
4)
42 [5, 7]
out
Floating-point number
(64 bits)
Analog Input
30 [6]
in
LReal
Q, M, DB
Analog Input Event
32 [6, 8]
in
LReal
Q, M, DB
Analog Output
41 [4]
out
LReal
Q, M, DB
Analog Output Event
4)
42 [6, 8]
out
Block of data (1...64
bytes)
5)
Octet String / Octet
String Output
110
[ - ] in, out
5)
DB
Octet String Event
5)
111 [ - ]
in, out
5)
DB
1)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 12.
2)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 20.
3)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 22.
4)
This object group can be configured in the Data point editor of STEP 7 using the substitute object group 41.
5)
With these data point types, contiguous memory areas up to a size of 64 bytes can be transferred. All S7 data types with
a size between 1 and 64 bytes are compatible.
Explanation of the table footnotes
1)
,
2)
,
3)
,
4)
: Configuring data points using substitute object
groups
The initial data point types of the following object groups can be configured using the
substitute object groups listed above:
10 [2]
11 [1, 2]
21 [1, 2, 5, 6]
23 [1, 2, 5, 6]
40 [1, 2, 3]
42 [1, 2, 4, 5, 6, 7, 8]
To configure the DNP3 CP, use the specified substitute object group.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET ET 200SP and is the answer not in the manual?

Siemens SIMATIC NET ET 200SP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET ET 200SP
CategoryNetwork Router
LanguageEnglish

Related product manuals