Characteristics
Table 4-3
X100 - X103 (SIMOTION D425, D435) or X100 – X105 (SIMOTION D445/D445-1)
Characteristic Type
Connector type DRIVE‑CLiQ connector (RJ45 socket)
Cable type DRIVE‑CLiQ standard (inside the control cabinet)
Cable type MOTION CONNECT (outside the control cabinet)
Maximum cable length 100 m
Dust protection filler plugs for
sealing unused DRIVE‑CLiQ ports
5 filler plugs contained in the D4x5 scope of delivery
Filler plugs (50 pcs) order number:
6SL3066-4CA00-0AA0
DRIVE‑CLiQ pin assignment
Table 4-4
DRIVE‑CLiQ interface (X100 - X103 or X100 – X105)
PIN Signal name Signal type Meaning
1 TXP O Transmit data +
2 TXN O Transmit data -
3 RXP I Receive data +
4 ---- ---- Reserved, do not use
5 ---- ---- Reserved, do not use
6 RXN I Receive data -
7 ---- ---- Reserved, do not use
8 ---- ---- Reserved, do not use
A + (24 V) VO Power supply for DRIVE-CLiQ, 450 mA maximum
B M (0 V) VO Ground to 24 V
Signal type: I = Input; O = Output; VO = Voltage Output
Additional references
●
SINAMICS S120 Control Units and Additional System Components
Manual
●
SINAMICS S120 Booksize Power Units
Manual
●
SINAMICS S120 for AC Drives
Manual
●
SINAMICS S120
Commissioning Manual
●
Terminal Modules TM15 and TM17 High Feature
Commissioning Manual
●
TM15/TM17 High Feature
Manual
For the order numbers, see the
Overview of SIMOTION documentation
(separate document)
Interfaces
4.2 DRIVE-CLiQ interfaces
SIMOTION D4x5
Manual, 04/2014 51