Table 8-1 Requirements of the DC power supply
Rated voltage According to EN 61131-2
Voltage range (mean value)
Voltage ripple, peak/peak
Ramp-up time when switched on
24 VDC
20.4 VDC to 28.8 VDC
5% (unsmoothed 6-pulse recti‐
cation)
any
Non-periodic overvoltages
Period of overvoltage
Recover time
Events per hour
≤ 35 V
≤ 500 ms
≥ 50 s
≤ 10
Transient voltage interruptions Downtime
Recovery time
Events per hour
≤ 3 ms
≥ 10 s
≤ 10
8.1.2 Grounding concept
Components
The SINUMERIK 840D sl system consists of a number of individual components which have been
designed so that the system complies with the appropriate EMC and safety standards. The
individual system components are:
• Numerical Control Unit (NCU)
• Machine Control Panel (MCP), Machine Pushbutton Panel (MPP)
• Keyboard
• Operator panels (operator panel front + TCU/PCU)
• Distributor box and handheld unit
• S7-300 I/O with IM 153 interface module
Grounding measures
The individual modules are attached to a metal cabinet panel. Insulating paints on the mounting
points (e.g. tension jacks) must be removed.
It is permissible to cluster the operator control components regarding connection/potential
bonding.
Example: The control panel on the swivel arm.
It is sucient in this instance to connect the ground connections of, for example, the PCU, TCU,
and operator panel front using a cable and to route a shared grounding conductor to the central
ground connection in the control cabinet.
Please note that interruption of the grounding during maintenance work is not permissible.