EasyManuals Logo
Home>Siemens>Relays>siprotec 7SD5

Siemens siprotec 7SD5 Manual

Siemens siprotec 7SD5
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Parameters and properties
27
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
Baud rate The PROFIBUS-DP slave of the SIPROTEC devices supports automatic baud rate
recognition. There are no settings necessary concerning the baud rate during the
parameterization of the SIPROTEC devices.
The baud rate is provided by the PROFIBUS-DP master.
The following baud rates are supported by the PROFIBUS communication modules:
Time
synchronization
GlobalSection.DP_TimeSyncEnable
If the time stamp mechanism of PROFIBUS System Management Service is used for
time synchronization of the SIPROTEC devices then the evaluation of time synchro-
nization messages from PROFIBUS has to be enabled on the communication module.
Ref. to chap. 4.4 for further information about parameter settings of time synchroniza-
tion via PROFIBUS.
Status bit for
metered
measurands
GlobalSection.DP_CountersWithStatus
Counters (metered measurands) are transferred via PROFIBUS-DP as unsigned long
values.
The meaning of the status bit (most significant bit of the unsigned long value) can be
defined with this paramter (ref. to chap. 3.6).
Note:
The DDB files/GSD files of the PROFIBUS-DP communication modules of the
SIPROTEC devices are enclosed within the parameterization system DIGSI:
DDB files/GSD files in the directory:
“...\SIEMENS\DIGSI4\MANAGER\S7DATA\GSD” or
“...\SIEMENS\STEP7\S7DATA\GSD” at installation of DIGSI and STEP7.
Associated Bitmap files:
“...\SIEMENS\DIGSI4\MANAGER\S7DATA\NSBMP” or
“...\SIEMENS\STEP7\S7DATA\NSBMP” at installation of DIGSI and STEP7.
Connection Supported baud rates
Isolated RS485 interface
(PSE module)
9.6; 19.2; 93.75; 187.5; 500; 1500; 3000; 6000 kB/s
Fibre-optical interface
(PSO module)
9.6; 19.2; 93.75; 187.5; 500; 1500 kB/s
Table 2-2 PROFIBUS communication moduls for SIPROTEC devices:
Supported baud rates
Note:
After baud rate change at the PROFIBUS-DP master a silent time of at least 2 sec-
onds is necessary on the bus so that the PROFIBUS-DP slave of the SIPROTEC
device can recognize the baud rate change and start the automatic baud rate recog-
nition again (short-time break of the bus connection at the PROFIBUS-DP master or
the like).

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals