Parameters and properties
26
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
2.1 Bus specific parameters
The following settings for the serial communication between the PROFIBUS-DP mas-
ter and the PROFIBUS-DP slave have to be defined during parameterization of the
SIPROTEC device.
Names written in MonoScriptText are the associated designations of the bus
specific parameters in the DIGSI parameterization software (ref. to chap. 4.1).
2.1.1 PROFIBUS-DP settings
Slave address GlobalSection.DP_Addr
Permissible PROFIBUS slave addresses for the SIPROTEC devices are in the range
between 1 and 126.
PNO identification
number
GlobalSection.DP_IdentNo
Depending on the chosen connection of the PROFIBUS net to the SIPROTEC device
(ref. to chap. 1.1 and 5) the PNO identification number of the communication module
has to be seleceted:
The DDB file/GSD file (corresponding to the PNO identification number) is necessary
for parameterization of the des PROFIBUS-DP master and describes the technical
characteristics of the PROFIBUS-DP slave device.
After importing the DDB file/GSD file in the parameterization system of the PROFI-
BUS-DP master the SIPROTEC modules with their device names are inserted in the
slave family
“Other field controller - SIPROTEC”.
Communication
module
PNO identifi-
cation number
Connection Device name
DDB file /
GSD file
PSE,
up to HW-Rev. 3
0x80A1
Isolated RS485
interface
"SIPROTEC4 - DP Modul" "siem80a1.gsd”
PSE,
from HW-Rev. 4
"SIPROTEC4 - DP Modul_HWRev4" "si1_80a1.gsd”
PSO,
up to HW-Rev. 3
0x80BC
Fibre-optical
interface
"SIPROTEC4 - DP Fibre" "siem80bc.gsd"
PSO,
from HW-Rev. 4
"SIPROTEC4 - DP Fibre_HWRev4" "si1_80bc.gsd"
Table 2-1 PROFIBUS communication modules for SIPROTEC devices:
PNO identification numbers, device names and DDB files/GSD files
Note:
You can continue to work also with the GSD file of the modules up to HW revision 3 if
a PROFIBUS communication module up to HW revision 3 is replaced with a PROFI-
BUS communication module from HW revision 4 (ref. to chap. 1.1) in an existing
installation
A changing of the PROFIBUS-DP master parameterization is not needed.