Parameters and properties
38
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
2.5 Event list via PROFIBUS-DP (Sequence of events recorder)
Attention!
1. This function was especially developed for application of the bay control unit
6MD663/6MD664 in conjunction with a substation master S5-155H in a HV DC
substation (high voltage DC transmission).
Other PROFIBUS-DP masters must be adapted if the function "Event list via
PROFIBUS-DP" is to be used (refer to item 4).
2. For the "Event list via PROFIBUS-DP" the following is required:
PROFIBUS-DP communication module firmware from V03.00.03,
a mapping file that supports "Event list via PROFIBUS-DP".
3. Please check in the bus mapping documentation of the SIPROTEC device (ref.
to page 3) that you are applying whether this device provides an "Event list via
PROFIBUS-DP".
4. To retrieve and evaluate the annunciations from the event list, the applied PROFI-
BUS-DP master must be programmed/set in accordance with the described
handshake mechanism (ref. to chap. 2.5.3) and data type definition (ref. to
chap. 3.9).
The required program sequences must be generated by the user.
5. The "Event list via PROFIBUS-DP" is not identical to the operational event log in
the SIPROTEC device, but is separately maintained on the communication
module.

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals