EasyManuals Logo
Home>Siemens>Relays>siprotec 7SD5

Siemens siprotec 7SD5 Manual

Siemens siprotec 7SD5
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Data type definitions
51
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
3.6 Metered measurand (unsigned long)
Number of
byte-values
4
Range of values 0 to +4294967295
Figure 3-6 Data type: Metered measurand (unsigned long)
Status bit (S) The status bit is set for invalid metered measurands in case of:
corruption of the metered measurand after device reset/device start-up
(the status bit is deleted after two update cycles of the metered measurand after
device reset/device start-up),
the external error bit of a pulse counter (metered measurand with a pulsed binary
input as source) is set.
Byte 3 (MSB) Byte 2 Byte 1 Byte 0 (LSB)
S
Metered measurand
Message head ... ... Message end
Note:
The overflow of the metered measurands is 7FFFFFFF
hex
+ 1 and the counter then
starts at 0 again.
The transmission of a status bit for metered measurands can be disabled in appli-
cation cases the metered measurand’s status bit is not required or if it could lead to
miscalculations in the PROFIBUS-DP master (ref. to chap. 2.1, Parameter
GlobalSection.DP_CountersWithStatus).
The status bit is always 0 if it is disabled.

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals