Parameters and properties
33
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
2.2.2 Transformer tap change commands
A transformer tap change command is applied via two outputs viz. two bits, which are
defined with "01" = LOWER and "10" = RAISE (ref. to chap. 3.7).
Feed-back information is obtained as transformer tap position indication (ref. to
chap. 3.8)
The transformer tap change command is output when the relevant bit pair via PROFI-
BUS-DP changes its value (an edge) from: "Quiescent status" or RAISE to LOWER
and "Quiescent status" or LOWER to RAISE (a definition of the "Quiescent status"
value is given in chapter 3.7).
To execute a number of tap changes sequentially, the initiation via PROFIBUS-DP
must be with impulses due to the fact that the command execution is edge triggered.
"Quiescent status" RAISE "Quiescent status" for raising the tap
"Quiescent status" LOWER "Quiescent status" for lowering the tap
The impulse length must be greater than the maximum bus-cycle time.
Information regarding the maximum bus-cycle time (also referred to as data cycle
time) can be found under the bus parameter settings of the PROFIBUS-DP master
parameterization system.
2.2.3 Behaviour under special operating conditions
A change of the switching device status which was not initiated by the PROFIBUS-
DP master (e.g. circuit breaker trip) is recognized by the PROFIBUS-DP master by
a change of the value of the switching device status in the corresponding bit posi-
tions of the input message.
If the PROFIBUS-DP master wants to reclose the locally switched off switching
device, then the current value (OFF) or "Quiescent status" must first be transmitted
via PROFIBUS-DP and then the switching device can be reclosed by setting the
must value (ON).
A switching operation requested via PROFIBUS-DP, which cannot be executed
(e.g. because the control authority is set to LOCAL or the corresponding interlock
conditions in the bay are not fulfilled) is recognized by the PROFIBUS-DP master
from a discrepancy between the checkback signal of the double command or the
status of the single command in the PROFIBUS-DP input message and the
requested switching status, or because the expected transformer tap change
checkback indication is not received.
A checkback supervision time may be activated in the PROFIBUS-DP master.
Before starting a new switching attempt, first the current switching status as per the
input message or "Quiescent status" has to be transmitted again in the output mes-
sage via PROFIBUS-DP.
The response in the event of disturbed communication is described in chap. 2.3.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT612 and is the answer not in the manual?

Siemens SIPROTEC 7UT612 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT612
CategoryProtection Device
LanguageEnglish

Related product manuals