EasyManuals Logo
Home>Siemens>Protection Device>SIPROTEC 7UT612

Siemens SIPROTEC 7UT612 User Manual

Siemens SIPROTEC 7UT612
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Data type definitions
52
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
3.7 Transformer tap change command (TC)
Number of
byte-values
1
/
4
(2 bits)
Range of values 0 (bit 1 = 0 and bit 0 = 0) - Quiescent status
1 (bit 1 = 0 and bit 0 = 1) - LOWER
2 (bit 1 = 1 and bit 0 = 0) - RAISE
3 (bit 1 = 1 and bit 0 = 1) - not permissible
Figure 3-7 Data type: Transformer tap change command
Notes for the execution of transformer tap change commands via PROFIBUS-DP may
be found in chapter 2.2.2.
Bit 1
TC 1TC 2
max. 4 TC per octet/byte
2
0
2
1
2
2
2
7
...2
4
Message head... ...Message end
Bit 0 Bit 1 Bit 0...
2
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT612 and is the answer not in the manual?

Siemens SIPROTEC 7UT612 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT612
CategoryProtection Device
LanguageEnglish

Related product manuals