EasyManuals Logo
Home>Smartgen>Controller>HMC6

Smartgen HMC6 User Manual

Smartgen HMC6
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
HMC6 Power Management Controller User Manual Page 47 of 87
No.
Items
Parameter Range
Default
Description
1: Enable
15
Set value
(90-150)%
130
16
Delay
(0.1-100.0)s
1.0
17
Alarm Type
(0-5)
2:Trip
18
Under Voltage
1 Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
19
Set value
(50-100)%
95
20
Delay
(0.1-100.0)s
5.0
21
Alarm Type
(0-5)
1:Warn
22
Under Voltage
2 Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
23
Set value
(50-100)%
80
24
Delay
(0.1-100.0)s
3.0
25
Alarm Type
(0-5)
2:Trip
26
Under Voltage
3 Set
Action
(0-1)
0: Disable
1: Enable
0:Disable
27
Set value
(50-100)%
70
28
Delay
(0.1-100.0)s
2.0
29
Alarm Type
(0-5)
2:Trip
30
Over
Frequency 1
Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
Setting value is busbar rated frequency’s
percentage, return value and delay value
can be set.
31
Set value
(100-130)%
105
32
Delay
(0.1-100.0)s
5.0
33
Alarm Type
(0-5)
1:Warn
34
Over
Frequency 2
Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
35
Set value
(100-130)%
110
36
Delay
(0.1-100.0)s
8.0
37
Alarm Type
(0-5)
2:Trip
38
Over
Frequency 3
Set
Action
(0-1)
0: Disable
1: Enable
0:Disbale
39
Set value
(100-130)%
120
40
Delay
(0.1-100.0)s
6.0
41
Alarm Type
(0-5)
2:Trip
42
Under
Frequency 1
Action
(0-1)
0: Disable
1:Enable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartgen HMC6 and is the answer not in the manual?

Smartgen HMC6 Specifications

General IconGeneral
BrandSmartgen
ModelHMC6
CategoryController
LanguageEnglish

Related product manuals