HMC6 Power Management Controller User Manual Page 64 of 87
started when the input is active.
The signal output when the controller is in remote
mode. The engine is remote control status when the
input is active.
Open breaker feedback input signal; Fail to Open
alarm will be initiated if the controller cannot detect
the signal after the input is active.
Simulate adjust voltage/frequency input is active
only when the input port is active.
Semi-start and auto start are inhibited.
External over current short circuit input trip.
Genset is inhibit to trip or shutdown except for over
frequency and over current.
Trip and stop immediately.
Configure the priority of controller as the highest
level.
If it failed to start, this input is active and will issues
start signal again.
When input is active, all gensets on the busbar
become manual mode.
When input is active, all gensets on the busbar
become semi-auto mode.
When input is active, all gensets on the busbar
becomes auto mode.
When input is active, all gensets on the busbar are
light load.
When input is active, all gensets on the busbar
become safe mode.
Semi-mode/Auto
Transfer Input
When input is active, auto mode is active;
When input is inactive, semi-auto mode is active.
Prohibit Genset
On-load Input
When input is active, in manual mode/semi-auto
mode, if genset capacity meets heavy consumer
request power, it will also output heavy consumer
response, heavy consumer allowed signal.
Limit Network
Connected No.
When input is active, limit genset network
connected number based on configuration (max.
network connected number);