EasyManuals Logo
Home>SMC Networks>Chiller>HRS018-A 20 R Series

SMC Networks HRS018-A 20 R Series User Manual

Default Icon
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
HRX-OM-W058
Chapter 5 Display and setting of various functions
5.16 Alarm customize function HRS-R Series
5-48
When "Automatic monitoring + Monitoring start timer" is selected
[1] Circulating fluid temperature when starting operation: Approximately 20
o
C
[2] Circulating fluid set temperature: 15
o
C
[3] "AS.21: Temperature alarm monitoring method": Select "Automatic monitoring + Monitoring
start timer".
[4] "AS.22: Monitoring start timer": Set it to "50 min".
[5] "AS.04: Detection temp. for the circulating fluid discharge temp. increase": Set to "16
o
C".
[6] "AS.06: Detection temp. for the circulating fluid discharge temp. drop": Set to "14
o
C".
[7] "AS.23: Range over detection timer": Set to "600 sec".
Fig 5.16-2 Alarm generation timing
-Alarm generation timing
Status (1): Start operation of the chiller. As the circulating fluid temperature is within the set
range of "AS.06", "AS.06" alarm monitoring starts.
Status (2): The circulating fluid temperature becomes within the set range of "AS.04".
"AS.04" alarm monitoring starts.
Status (3): The circulating fluid temperature exceeds the threshold of "AS.06", but the alarm
will not be generated as it has returned within the 600 sec range of the "AS.23:
Range over detecting timer".
Status (4): The circulating fluid temperature exceeds the threshold of "AS.04", but the alarm
will not be generated as it has returned within the 600 sec range of the "AS.23:
Range over detecting timer".
Status (5): 50 minutes passes after starting operation. Alarm monitoring has started. It
shows that the "50 min" setting does not influence the alarm monitoring under
these conditions.
Status (6): Alarm will be generated after 600 seconds that is set for "AS.23: Range over
detection timer" after the circulating fluid temperature exceeds the threshold of
"AS.04".
Thermo chiller
Run
Stop
Circulating fluid
set temperature
15
o
C
AS.04 Alarm monitoring
ON
OFF
Alarm
Generation
Nothing
50min
600sec
Circulating fluid
temperature
ON
OFF
250sec
500sec
Elapsed time
AS.04
set temperature 16
o
C
AS.06
set temperature 14
o
C
1
2
4
3
5
6
AS.06 Alarm monitoring

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS018-A 20 R Series and is the answer not in the manual?

SMC Networks HRS018-A 20 R Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRS018-A 20 R Series
CategoryChiller
LanguageEnglish

Related product manuals