EasyManuals Logo

SMC Networks HRS018-A 20 R Series User Manual

Default Icon
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #93 background image
HRX-OM-W058
Chapter 5 Display and setting of various functions
HRS-R Series 5.16 Alarm customize function
5-35
●AL19 Communication error (Refer to Table 5.16-12 and Table 5.16-13)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
Not to detect is default setting.
Threshold change: Time at which this alarm is generated can be
changed.
30sec" is default setting.
AL31 Contact input signal 1 detection(Refer toTable 5.16-14)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
"Operation continue" is default setting.
●AL32 Contact input signal 2 detection (Refer to Table 5.16-15)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
"Operation continue" is default setting.
●AL21 DC fuse cutRefer to Table 5.16-16
Operation: When this alarm signal is output, user can choose to
stop/continue the operation.
"Operation stop" is default setting.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS018-A 20 R Series and is the answer not in the manual?

SMC Networks HRS018-A 20 R Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRS018-A 20 R Series
CategoryChiller
LanguageEnglish

Related product manuals