HRX-OM-W058
Chapter 7 Alarm indication and trouble shooting
7.4 Other Errors HRS-R Series
Table 7-2 Alarm code list and Troubleshooting (2/2)
Cause / Remedy
(Press the reset key after eliminating the cause.)
The timing of a periodical check is
informed.
Recommended to ask for the check
and service of the pump, fan motor
and compressor.
*Refer to’’5.18 Accumulated time
reset function’’.
Every 20,000 hours
(Option T: Every
8,000 hours)
4
Maintenance of compressor
Contact input1 signal
detection
3
Contact input is detected.
Contact input 2 signal
detection
3
1: ’’Stop” or “Continued” are default settings. The user can change them to “Continued” and “Stop”. For details, refer
to ’’5.16 Alarm customize function’’.
2:”AL19, Communication error” is disabled in the default setting. When this function needs to be enabled, refer
to ’’5.19 Communication function’’.
3: The functions of “AL31 Contact input 1 Signal detection” and “AL32 Contact input 2 Signal detection” are not
default settings. If these functions are used, refer to “5.19Communication function”.
4: Notice on mechanical seal replacement. Mechanical seal replacement is limited to 2 times. If the cumulative
operation time of the pump exceeds 20,000 hours, please consider requesting pump inspection service.
7.4 Other Errors
How to check other errors
The causes and remedies for failures that are not indicated by alarm
numbers are shown in ’’Table 7-3’’.
Table 7-3 Causes and remedies for failures without alarm number
The operation panel
displays nothing
No power supply
(The breaker for the power supply is not
turned on.)
Trip of breaker due to short-circuit and
current leakage
Repair the short-circuit or current leaking
part.
The [RUN] LED does
not light up even
when the
[RUN/STOP] switch is
pressed.
Check the presence of communication
setting.
Failure of the [RUN/STOP] switch