HRX-OM-O021
Chapter 5 Display and setting of various functions
HRS Series 5.21 Option [Electric resistivity sensor set]
5-75
5.21.2 Option [Electric resistivity sensor set] setting and checking
The table below explains the setting items of the option [Electric resistivity
sensor set] and the initial values.
Table 5.21-1 List of set electric resistivity sensor set [Option]
Display Item Contents
Initial value
(Default setting)
Option [Electric
resistivity sensor
set]
Set the
Option [Electric resistivity
sensor set]
mode to valid / invalid.
OFF
1. Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for key-lock [
] appears on the
digital display.
PV
SV
PV
SV
PV
SV
Electric resistivity sensor set [Option] Setting and checking
2. Press the [SEL] key 18 times.
The set screen of electric resistivity sensor set [Option] is displayed on the digital display.
PV
SV
3. Select electric resistivity sensor set [Option] from the table below with [▲] key or [▼] key,
and confirm by pressing “SEL”.
Table 5.21-2 List of set value
Set value Explanation
Initial value
(Default setting)
Option [Electric resistivity sensor set]mode
to invalid
○
Option [Electric resistivity sensor set]mode
to valid
4. Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV
[MENU]
Press and
hold
[MENU]
Press and
hold