HRX-OM-O021
Chapter 5 Display and setting of various functions
HRS Series 5.7 Signal for completion of preparation (TEMP READY)
5-19
5.7 Signal for completion of preparation (TEMP
READY)
5.7.1 Signal for completion of preparation (TEMP READY)
This function sets the band width for the circulating fluid set temperature
(upper/lower temperature range) in order to notify the customer by
communication that the circulating fluid temperature has reached the band
range (upper/lower temperature range).The default setting of this function is
“OFF”.
Tips
This function is available when contact input/output and serial communication
is used. Refer to the Communications Operation Manual for more details.
An example is shown below.
Circulating fluid set temperature
20
o
C
READY band width (upper/lower
temperature range)
±2
o
C
READY time
60 sec.
Preparation is completed 60 seconds after the circulating fluid temperature
reaches 18
o
C to 22
o
C.
Circulating set fluid 20
READY TEMP 22
READY TEMP 18
READY band width
upper/lower temperature range 2
READY band width
upper/lower temperature range 2
Circulating set fluid
READY time
60sec
Completion
of preparation
READY time
lower than 60sec
Contact outputState generation output
SerialON output
Contact outputState not generation output
Serial OFF output
Completion of preparation
TEMP READY

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS050-A*-20 Series and is the answer not in the manual?

SMC Networks HRS050-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRS050-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals