HRX-OM-O021
Chapter 7 Control, Inspection and Cleaning
HRS Series 7.2 Inspection and Cleaning
7-3
7.2.2 Monthly check
Cleaning of air vent (For air-cooled type)
Use a long bristled brush or air gun to clean the condenser to prevent the fins
from being deformed or damaged.
Removal of the dustproof filter
1. The dustproof filter is installed at the lower part of the front face of the thermo-chiller. It is
mounted with a magnet.
The dustproof filter is divided into two sections. They are identical.
2. They can be removed as shown in the drawing below.
Care should be taken not to deform or scratch the air-cooled condenser (fin) while the
removal.
Fig. 7-1 Removal of the dustproof filter
Cleaning of filter
Use a long bristled brush or air gun to clean the condenser.
Fig. 7-2 Cleaning of filter
If the fins of the air-condenser become clogged with dust or debris, heat radiation
performance reduces. This results in the reduction of cooling performance, and
may stop the operation because the safety device is triggerShut off the power
supply of the product when performing cleaning, maintenance or inspection. It
might cause electric shock, injury or burn, etc.
Replace all panels removed for inspection or cleaning. It might cause injury or
electric shock if it is o
p
erated with the
p
anel removed or o
p
ened.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS050-A*-20 Series and is the answer not in the manual?

SMC Networks HRS050-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRS050-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals