HRX-OM-Q026
Chapter 3 Transport and Setting Up
HRSH Series 3.1 Transport
3-1
Chapter 3 Transport and Setting Up
3.1 Transport
The product is heavy and has potential danger at transport. Also, to prevent
damage and breakage of the product, be sure to follow the instructions
shown below for transport.
Drain the residual fluid from the piping as much as possible to
prevent any spillage.
Only persons who have sufficient knowledge and experience about
the product and system are allowed to transport and set up the
product.
Especially pay attention to personal safety.
Never lay the product on its side.
The compressor oil will leak in to the refrigerant piping, which may
cause early failure of the compressor.
When the product is carried by using a forklift, make sure that the
fork does not damage the cover panel or piping port.
Be sure to use all the four eye bolts when slinging the product.
The slant angle of each rope should be 60 degrees or less.
When moving the product by a forklift, insert the fork into the right
positions referring to 3.1.1 Transportation using forklift and
hanging- Moving by forklift and slinging should be done by
persons who have the licenses.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH250-W*-20 Series and is the answer not in the manual?

SMC Networks HRSH250-W*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH250-W*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals