-20-
No.PS※※-OMM0007-H
■Wiring
○Connection (Refer to page 22 for products with M8 (3 pin) connector)
Connections should only be made with the power supply turned off.
Use a separate route for the product wiring and any power or high voltage wiring. Otherwise, malfunction
may result due to noise.
○Internal circuit and wiring example
-S/-R
(Analogue output mode)
Switch output
NPN open collector output type-2 output
Max. 28 V, 80 mA
Residual voltage 1 V or less
R: Analogue output 1 to 5 V
Output impedance 1 k
S: Analogue output 4 to 20 mA
Max. load impedance
Power supply voltage 12 V: 300
Power supply voltage 24 V: 600
Min. load impedance 50
-S/-R
(Auto-shift input mode)
With auto-shift switch output
NPN open collector output type-2 output
Max. 28 V, 80 mA
Residual voltage 1 V or less
-X
(Copy function switch output)
NPN open collector output type-2 output
Max. 28 V, 80 mA
Residual voltage 1 V or less