Page #50 background image
-49-
No.PS※※-OMM0007-H
Other Settings
Peak/Bottom hold value display
The maximum (minimum) pressure from when the power was supplied to this moment is detected and
updated. In peak/bottom display mode, this pressure is displayed.
For the peak display, when the button is pressed for 1 second or longer, the maximum pressure and
"Hi" starts flashing, and is held.
To release holding the display of the maximum pressure, press the button for 1 second or longer again
to return to measurement mode.
For the bottom display, when the button is pressed for 1 second or longer, the minimum pressure and
"Lo" starts flashing, and is held.
To release holding the display of the minimum pressure, press the button for 1 second or longer again
to return to measurement mode.
If the and buttons are pressed simultaneously for 1 second or longer while the pressure is being held,
the maximum (minimum) values are reset.
Zero clear
A displayed value can be adjusted to zero when the pressure to be measured is within 7% F.S. (3.5%
F.S. for compound pressure) of the pressure, at the time of shipment from the factory.
(A tolerance range of 1% F.S. may apply due to individual product differences).
Press the and buttons simultaneously for 1 second or longer, to clear the display to "0".
The display will return to measurement mode automatically.
For analogue output, the analogue output will be changed with the display.
Key lock
The key lock function is used to prevent errors occurring due to unintentional changes of the set values.
If the button operation is performed while key lock setting is ON, "LoC" is displayed for approximately 1
second.
(When the button is pressed, the set pressure will be displayed following "LoC").
<Operation - Without security code input- >
1, Press the button for 5 seconds or longer in measurement mode.
The current setting "LoC" or "UnL" is displayed.
(Selecting or releasing the key lock is carried out in a similar way).
2, Press the or button to select key lock (or key unlock).
3, Press the button to store the setting.