The pressure
display accuracy
does not satisfy
the
specifications.
Check if any foreign matter has
entered the piping port.
Install a 5 m filter to
prevent foreign matter from
entering the piping port.
Also, clean the filter
regularly to prevent
drainage deposits.
Check if air or fluid are leaking from
the piping.
Rework the piping.
If an excessive tightening
torque is applied, the
mounting bracket, screws or
the product may be
damaged.
Insufficient
warm-up time
Check if the product satisfies the
specified accuracy after 10 minutes
warm up time.
After energizing, the display
and output can drift. For
detecting fine pressures,
warm up the product for 10
to 15 minutes.
The display units
cannot be
changed.
Improper model
selection
(selection of
model "without
units selection
function")
Check if there is an "-M" at the end
of the part number printed on the
product
"M" in the part number
means that the units cannot
be changed.
(kPaMPa can be selected)
: The units selection function
is not available in Japan due
to a new measurement law.
: It is fixed to the SI unit "kPa",
"MPa".
The buttons
cannot be
operated.
Check if the key lock mode is turned
on.
Turn off the key lock mode.
Check that the panel mount adapter
and the product are correctly
assembled.
Mount the product on the
panel correctly.
Check if air or fluid are leaking from
the piping.
Rework the piping.
If an excessive tightening
torque is applied, the
mounting bracket, screws or
the product may be
damaged.
Copy function
error
Unable to copy
(1) Check the wiring connection at
the FUNC terminal.
(2) Check the power supply wiring.