○Error indication
This function is to display error location and content when a problem or an error occurs.
The switch output load current is
more than 80 mA.
Turn the power off and remove the
cause of the over current.
Then turn the power on.
During zero clear operation, pressure
above ±7%F.S. (±3.5%F.S. for
compound pressure) has been
applied. After 1 second, the mode will
return to measurement mode. The
zero clear range can vary ±1%F.S.
with individual product differences.
Perform zero clear operation again
after restoring the applied pressure to
an atmospheric pressure condition.
Pressure has exceeded the upper
limit of the set pressure range.
Reset applied pressure to a level
within the set pressure range.
Pressure has exceeded the lower
limit of the set pressure range.
The measured pressure at auto-shift
input exceeds the set pressure
range.
: After 1 s, measurement mode returns
automatically.
Auto-shift input is invalid.
Check the connected equipment and
machine.
Displayed in the case of an internal
data error.
Turn the power off and turn it on
again.
If resetting fails, an investigation by
SMC Corporation will be be required.
If the error can not be reset after the above measures are taken, then please contact SMC.