12.4.
The commissioning must always result in having at least 1 LED source available lit..
Therefore, the voltage and frequency must be within the defined thresholds.
Any action on the potentiometers changes the settings, even if the cover is closed.
12.4.1. Single phase version
Source LED ON LED OFF LED blinking
Source 1 available Source 1 not available
or out of range
- a timer is counting
down
- test mode
Source 2 available Source 2 not available
or out of range
- a timer is counting
down
Source availability LED
• E: No stop in O position
• F: 2s stop in O position
Stop in 0 position: E-F
• G: Network - Genset
• H: Network - Network
Type of application: G-H
Dip switch settings
LED info
A
E
Fault reset
Loss of priority source timer
FT: 0-60 sec.
FT
RT
U/F
[HYST]
[HYST]
RT: 0-30 min.
U/F
Timer settings
C
Return of priority sourcetimer
LED ON LED OFF LED blinking
Fault Product OK or
S1-S2not available
Please wait
Auto mode Manual mode Manual retransfer
Fault and state of the product LED's
Hysteresis settings
B
HYST: 20 %DU/F
DU: 5-20%
DF: 3-10%
Source supply voltage
andfrequency
Auto-Configuration
D
LED state Auto Conf result Action
Steady ON OK Ready
Blinking Not OK Repeat step D
Ensure that the supply
voltage is available and
within the following limits:
Un: 176-288VAC
Fn: 45-65Hz
Press PROG for ≥ 2s