39
EN
12.4.2. Thr
ee phase version
FT
Source LED ON LED OFF LED blinking
Source 1
available
Source 1
missing or
out of
range
- a timer is
counting
down
- test mode
Source 2
available
Source 2
missing or
out of
range
- a timer is
counting
down
Source availability LED
• E: No stop in O position
• F: 2s stop in O position
Stop in 0 position: E-F
• C: 50 Hz
• D: 60 Hz
Frequency: C-D
• A: 3P
• B: 1P
Type of network: A-B
• G: Network - Genset
• H: Network - Network
Type of application: G-H
HYST: 20 %DU/F
DU: 5-20%
DF: 3-10%
Dip switch settings Led info
A
Source voltage
supply configuration
B
Loss of priority source timer
127/230 Vac version 230/400 Vac version
Un (P-P):
208-240 Vac
Un (P-N):
120-138 Vac
Un (P-P):
380-420 Vac
Un (P-N):
220-240 Vac
FT: 0-30 sec.
U/F
[HYST]
[HYST]
RT: 0-30 min.
U/F
Timer settings
C D
Fault reset
Return of priority sourcetimer
LED ON LED OFF LED blinking
Fault Product OK Wait
Auto mode Manual
mode
Manual
retransfer
Fault and state of the product Leds
RT