Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control
Firefighter Gateway Installation Guide MAN-01-00113-1.2
17
Clr Alarm Mode: Select the method to return to normal operation as soon as the emergency stop
button is released:
Automatic (default) when releasing the stop button or relay, the system immediately returns
to normal power production.
Manual when releasing the stop button or relay, the system will not return to normal
operation unless the user manually clears the alarm by selecting Clear Alarm (below). Use this
option if the button does not have the locking feature, the relay in the control system may
open unexpectedly, or if the user requires this added step.
Clear Alarm: Used to allow normal operation. Appears only if the Clr Alarm Mode parameter (above)
is set to Manual, and the installation is in remote safety shutdown