10.2.1.3 Local Power Control
If active dispatching instruction or dispatching target value is used as dispatching input
locally, the active control mode is set to "Local power control".
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Local power control".
step 3 Set local dispatching parameters. For specific parameter description, refer to the
following
table 10-2 Parameter description
PPaarraammeetteerr
DDeessccrriippttiioonn
Communication abnormality
output (%)
Communication is abnormal, and specified dispatch
output value is delivered.
Control method
Open loop control:At the start time, the locally
configured active instruction is sent to the power
output port of the inverter, thereby implementing
active power control.
Closed-loop control:
In case no Smart Energy Meter is selected, at the
beginning time, the active instruction configured
locally is used as target value, and active power
compensation ratio is calculated and sent to the
power output port of the inverter. Generally, this
strategy is used for fast and accurate active
power regulation.
In case a Smart Energy Meter is selected, at the
beginning time, active instruction configured
locally is used as target value, active power of the
meter needs to be collected and used as input
parameter, and active power compensation ratio
is calculated and sent to the power output port of
the inverter. Generally, this strategy is used for
anti-backflow or avoiding zero power feed-in.
Select energy meter*
Unselected
Select Smart Energy Meter involved in power
regulation
Control cycle
Time interval of delivering dispatching instructions
Parameter range: 5~60s
Q-Method
kW: set active power value
%: set active power percentage
Note: *Only when the control method is set to "Closed-loop control", the parameter "-
Select energy meter" is settable.
User Manual 10 Grid Dispatching