Operation
|
17
11 Operation
Safety information
Warning: Hazard from electrical voltage or moving components.
The device may only be operated by adequately qualified persons, details see Table 1 Qualifications, page 2.
Only use the fan in accordance with the operating instructions and the operating instructions for the motor.
12 Troubleshooting/maintenance/repair
Safety information
Troubleshooting/maintenance/repair may only be carried out by adequately qualified persons, details see Table 1
Qualifications, page 2.
Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2.
The impeller must be at a standstill.
12.1 Troubleshooting
Table 15 Troubleshooting
Problem Possible causes
Remedy
Fan does not run
smoothly
Impeller imbalance
Rebalancing by a specialist company if possible,
otherwise contact Systemair.
Soiling on the impeller Clean carefully, rebalance
Material decomposition on the
impeller due to aggressive
material conveyed.
Contact Systemair
Impeller rotates in wrong
direction.
Change direction of rotation if possible, otherwise contact
Systemair.
Deformation of impeller due to
excessive temperature.
Ensure that the temperature does not exceed the certified
value/Install new impeller.
Vibrations, oscillations
Check the installation of the fan/check the duct system,
see 8 Installation, page 11.
Air output of fan too
low
Impeller rotates in wrong
direction.
Change direction of rotation if possible, otherwise contact
Systemair.
Wrong wiring configuration (e.g.
Y instead of Delta).
Check and possibly correct the wiring configuration.
Pressure losses too high. Optimize the line routing.
Flow regulators not or only
partly open.
Check opening position on site.
Intake or pressure ducts are
blocked.
Remove the blockage.
Grinding sounds
when starting or
operating the fan
Check if the duct connections of
the fan are strained.
Loosen the duct connections and realign it.
Thermal contacts/
resistors have
triggered
Impeller rotates in wrong
direction.
Change direction of rotation if possible, otherwise contact
Systemair.
Missing phase
In case of a 3 phase standard motor (not EC), check if all 3
phase are present.
Motor overheated
Check the cooling impeller (if used), measure the motor
winding (if possible) / contact Systemair.
Capacitor (if used) not or not
correctly connected.
Connect the capacitor correctly.
Motor blocked
Contact Systemair
| 005

Other manuals for SystemAir DVS series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir DVS series and is the answer not in the manual?

SystemAir DVS series Specifications

General IconGeneral
BrandSystemAir
ModelDVS series
CategoryFan
LanguageEnglish

Related product manuals