AccuLoad IV Installation & Maintenance Manual
Installation 19
3.3.3 Cable Entries
All cable entries must meet the requirements of ABNT NBR IEC 60079-1, summarized as follows:
Any installation accessories used in the cable entries (such as cable glands, adapters, or bushings) must
be Ex d certified. The cable ends must be properly installed and adequately protected against
mechanical damage.
For wiring systems using conduits, a certified sealing unit must be used immediately at the entrance of the
enclosure. Any unused input must be correctly closed with a certified device that guarantees the type
and degree of protection (IP65).
3.3.4 Cover Fasteners
The EX d enclosure requires cover mounting bolts to be M8 x 1.25-6g, DIN 912, steel grade 12.9.
3.3.5 Grounding
The touch-screen user interface (if provided) is protected by an intrinsic safety barrier, the Ex d enclosure
must be grounded in accordance with national electrical code regulations.
The ground connection must be made through the external ground terminal of the Ex d enclosure. An
external connection is not necessary when using metal conduits or shielded cables.
The cross section of the external ground wiring must be 10 to 12 AWG (5.26 mm
2
to 3.31 mm
2
wire).
3.4 ALIV SA Installations
The AccuLoad IV SA model is comprised of the following units:
One FCM unit that contains all of the I/O control electronics connected to peripheral hardware, such as
meters, valves, and permissives
One or two MMI units that act as the operator control panels
North American Division 2 and Zone 2 installation requirements must be followed for the installation of
the AccuLoad IV N4 and SA equipment; substitution of components may void safety certifications.
Compliance with local codes is mandatory.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TechnipFMC Smith Meter AccuLoad IV and is the answer not in the manual?

TechnipFMC Smith Meter AccuLoad IV Specifications

General IconGeneral
BrandTechnipFMC
ModelSmith Meter AccuLoad IV
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals