TK 61651-18-OP-EN
29
Pharma
Single and Multi-temperatures temperature Units qualified for
pharmaceutical applications under Thermo King protocol are configured
with specific Pharma configuration file and parameters loaded during
commissioning by your local dealer. Evaporators fans have to run during the
Null Cycle.
ThermoKing recommends to run the unit with the recommended Setpoints
below:
Table 1. Single Temperature units:
Temperature Range
Recommended
Setpoint
Max Deviation Setpoint
Temperature between +15°
C and +25°C
+20°C
+1/- 2°C of setpoint
Temperature between 15°C
and 25°C
+5°C +/- 2°C of setpoint
Table 2. Multi-Temperature units:
Temperature Range
Recommended
Setpoint
Max Deviation Setpoint
Temperature between +15°
C and +25°C
+20°C
+/- 2°C of setpoint
Temperature between 15°C
and 25°C
+6°C +/- 2°C of setpoint
Efficient loading practices and operating procedures have to be followed to
ensure optimum air circulation and temperature management.