Unit Start-up
Pre-Start Checklist
Complete each step in the checklist that follows and check off each step as com-
pleted. When all are accomplished, the unit is ready to run.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the power
can not be inadvertently energized. Failure to disconnect power before
servicing could result in death or serious injury.
CAUTION
Possible Equipment Damage!
To prevent overheating at connections and under-voltage conditions at
the compressor motor, check tightness of all connections in the
compressor power circuit.
To prevent compressor damage, do not operate the unit with discharge
or liquid line service valves closed.
The use of untreated or improperly treated water in a Chiller may result
in scaling, erosion, corrosion, algae or slime. It is recommended that the
services of a qualified water treatment specialist be engaged to
determine what water treatment, if any, is required. The Trane Company
assume no responsibility for equipment failures which result from
untreated or improperly treated water, or saline or brackish water.
To prevent evaporator or condenser damage, pipe strainers must be
installed in the water supplies to protect components from water born
debris. Trane is not responsible for equipment-only-damage caused by
water born debris.