Startup Test Log
AFDK-SVU01C-EN 53
Water-Cooled CenTraVac Chiller with
CH530/CH531 Control and Adjustable
Frequency Drive
(AFD) Starter
Job Name AFD Serial Number
Job Location AFD Model Number
Sales Order Number Ship Date
Chiller Serial Number Start Date
Chiller Model Number
Starter Date: TechView™: Setpoint View: AFD Default Setting
Manufacture AFD Control Auto
Type AFD Re-Optimization Sensitivity 10%
Vender ID
Model Number
TechView: Configuration View:
Starter Type: AFD
Trane
Default
Setting
Volts & Hz
Amps Surge Detections enable
Motor Data: Surge Sensitivity 20
Manufacturer Power Loss Reset Time 60
Type & Frame Motor NP Volts 460
Drawing # Motor NP FLA (TVA) 0
Serial Number Motor NP RLA 1
Nameplate Data: Motor NP Power 0
RLA Motor NP Hertz 60
KW Motor NP PRM (TRPM) 3600
Volts & Hz Stator Resistance (SRES) 0
Prestart Checks Date Checked Flux Current Ref. (FAMP) 0
Motor Grounded Acceleration Time 30
Motor Rotation Deceleration Time 30
Drive Chassis Grounded Current Limit 1
Control Wiring Tight Current Limit Gain 10
Drive Connections are Tight Power Loss Mode Decel
Verified Settings Power Loss Time 0
Flying Start Enable disable
Comments: Flying Start Gain 2000
Use Trane Defaults (for all other AFD
parameters not accessible via TechView)
Test Log Date:
TechView Status View: Motor Log 1 Log 2
% RLA Average
Amps Average
Volts Average
Load PF
Power KW
Winding #1 temp
Winding #2 temp
Winding #3 temp
AFD Speed
AFD Freq
AFD Transistor temp