AFDH Drive Package Specifications
AFDH-SVN03H-EN 19
Remote Mount Weights and Heat
Rejection
Table 8. AFDH D-Frame remote mount unit weights (460 V/480 V)
460 V/V480 V D-Frame AFDH
Catalog/Maximum
(a)
Amps
281 Catalog/
301 Maximum
336 Catalog/
361 Maximum
413 Catalog/
443 Maximum
500 Catalog/
535 Maximum
Unit Weight
652 lb 695 lb 767 lb 1088 lb
Heat Rejection
14,300 Btu/h 16,380 Btu/h 19,800 Btu/h 24,450 Btu/h
(a)Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
Table 9. AFDH D-Frame remote mount unit weights (380 V/400 V)
380 V/400 V D-Frame AFDH
Catalog/Maximum
(a)
Amps
293 Catalog/
315 Maximum
367 Catalog/
395 Maximum
446 Catalog/
480 Maximum
545 Catalog/
588 Maximum
Unit Weight
652 lb 695 lb 767 lb 1088 lb
Heat Rejection
14,300 Btu/h 16,380 Btu/h 19,800 Btu/h 24,450 Btu/h
(a)Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
Table 10. AFDH D-Frame remote mount unit weights (575 V/600 V)
575 V/600 V D-Frame AFDH
Catalog/Maximum
(a)
Amps
178 Catalog/
192 Maximum
226 Catalog/
242 Maximum
271 Catalog/
290 Maximum
321 Catalog/
344 Maximum
374 Catalog/
400 Maximum
Unit Weight
652 lb 695 lb 695 lb 767 lb 1088 lb
Heat Rejection
11,262 Btu/h 14,300 Btu/h 16380 Btu/h 19,800 Btu/h 24,450 Btu/h
(a)Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.