Installation
AFDH-SVN03H-EN 41
Reprogramming Factory Installed Tracer
AdaptiView Controls (CTV Firmware)
Important: Make sure your laptop is loaded with the
most current version of Tracer® TU tool
software so that you have the most up-to-
date version of CTV MP firmware available
to install into the UC800.
Note: CTV MP firmware is always used in factory installed
Tracer® AdaptiView™ control systems or in
Tracer® AdaptiView™ display upgrades to factory
installed CH530 control systems.
Table 17. UC800/Tracer AdaptiView CTV parameter values with a retrofit AFDH
Tracer TU Service Setpoints View:
Adjustable Frequency Drive Setpoints
Range Default Setting Recommended Setting
AF Control Auto, Fixed Auto Auto
ReOptimization Sensitivity 0–100% 20 20
Tracer TU Field Startup View:
Adjustable Frequency Drive
Range Default Setting Recommended Setting
Maximum Frequency 38–60 Hertz 60 60
Minimum Frequency 38–60 Hertz 38 38
AFD Surge Capacity Increase 0–5% 1 1
Tracer TU Configuration View: Main Range Default Setting Recommended Setting
Unit Type (MODL) CVHE, CVHF, CVHG, CVGF CVHE
Enter Chiller Model from Unit Nameplate
(Note: only CVHE or CVHF apply)
Tracer TU Configuration View: UC800
Range Default Setting Recommended Setting
Starter Type Not Applicable Unit Mount Wye-Delta Remote Mount Non-Comm AFD
Impeller Diameter (CPIM) 210–335 275 Enter CPIM from Unit Nameplate
Tracer TU Configuration View: Starter Range Default Setting Recommended Setting
Stop Delay Time (Contactor Interrupt Failure) 1–30 Seconds 3 30
Unit Voltage 180–15000 Volts 460 Enter from Unit Nameplate
Voltage Transformer Ratio 0–700 20 Enter from Unit Nameplate
Rated Load Amps (RLA) 0–2500 Amps 500 Enter from Unit Nameplate
CT Meter Scale 0–2000 0 Choose Correct CT Meter Scale from
Table 15, p. 39
Current Unbalance Trip Point 15–100% 30 30
Current Unbalance Grace Period 10–255 Seconds 90 90
Maximum Acceleration Setting 6–64 Seconds 6 30
Acceleration Time Out Action Shutdown, Transition Shutdown Shutdown
Overload Type Exponential, Linear Linear Linear
Phase Reversal Enable, Disable Enable Disable
Contactor Integrity Test Enable, Disable Disable Disable
Phase Reversal Grace Period 20–1000 milliseconds 700 1000
Surge Protection Enable, Disable Enable Enable
Momentary Power Loss Protection Enable, Disable Enable Disable
Restart Inhibit Stop to Start Time 0–255 Seconds 30 60
Surge Sensitivity 0–100% 20 20
Power Loss Reset Time 0–255 Seconds 15 15
RTD Type 75 Ohm@75F, 100 Ohm@ 0C 75 Ohm 75 Ohm