RT-SVX072A-EN
Figure 43. Supply fan performance with variable frequency drive 30 ton cooling only, 20/25 ton gas heat - direct
drive plenum, 80% width
2000 RPM
1900 RPM
1800 RPM
1700 RPM
1600 RPM
1500 RPM
1400 RPM
1300 RPM
1200 RPM
1100 RPM
1000 RPM
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
Sta!c Pressure, Inches w.c.
Airflow, CFM
IImmppoorrttaanntt:: Maximum static pressure leaving the
rooftop is 4.0" H
2
O positive. The static
pressure drops from the supply fan to the
space cannot exceed 4.0" H
2
O.
NNootteess::
Shaded areas represent selectable area.
Contact your local Trane
®
representative for
more information.
Supply fan performance curve includes
internal resistance of rooftop. For total static
pressure determination, system external
static must be added to appropriate
component static pressure drops
(evaporator coil, filters, optional economizer,
optional relief fan, optional heating system,
optional cooling only extended casing,
optional roof curb).
Maximum Cfm (for cULus approval) as
follows: 30 ton - 13,500 Cfm.
Minimum motor horsepower is 3 hp.
Maximum motor horsepower is 20 hp.
Maximum fan RPM is 2200.
UUnniitt SSttaarrttuupp

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak 1 and is the answer not in the manual?

Trane IntelliPak 1 Specifications

General IconGeneral
BrandTrane
ModelIntelliPak 1
CategoryAir Conditioner
LanguageEnglish

Related product manuals