Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVX051A-GB
37
Installation – Mechanical (Water pumps)
Multi-Pipe unit can be ordered with optional integrated hydraulic modules, provided with the following components
factory mounted and tested:
Centrifugal water pump, Low pressure or High pressure (option)
Water strainer to protect the pump against impurities in the circuit
Expansion module with expansion vessel and pressure relief valve sufficient to ensure the expansion of the
water loop ability (chilled water pump only)
Thermal insulation for antifreeze protection
Variable speed drive (Optional) for equilibrate the flow of water circuit
Drain valve
Temperature sensor
Note: A pressure switch device to detect lack of water is not included in the pump package. Installation of this type of
device is highly recommended to avoid sealing damage due to operation of pump without enough water.
Pump package schematics is supplied in the documentation set shipped with the unit.
Integrated pump package

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Sintesis Balance CMAF and is the answer not in the manual?

Trane Sintesis Balance CMAF Specifications

General IconGeneral
BrandTrane
ModelSintesis Balance CMAF
CategoryChiller
LanguageEnglish

Related product manuals