4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVX051A-GB
8
Digit 41 – Factory tests
X = None
B=Visual Inspection with customer
C=Performance test with customer: 1 point
(Cooling and Heat recovery mode)
D=Performance test with customer: 2 points
(Cooling and Heat recovery mode)
E=Performance test with customer: 1 point
(Cooling and Heat recovery mode)
S = Special
Digit 42 – Unit isolation
X = None
1 = Neoprene Isolators
4 = Neoprene pads
Digit 43 – Literature language
B = Bulgarian
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
K = Finnish
L = Danish
M = Swedish
N = Norwegian
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
Z = Slovene
2 = Romanian
3 = Serbian
4 = Slovak
5 = Croatian
6 = Hungarian
8 = Turkish
Digit 44 – Shipping package
X = Standard protection
A = Containerization package
Digit 45 – Refrigerant
X = None
A = R410A Factory full Refrigerant charge
8 = R410A Factory Refrigerant Pre-Charge
Digit 46 – Isolator Valve per Manifold Compressor
A = With (Discharge and Liquid)
Digit 47 – Power Factor Correction Capacitors
X = None
A = With
Digit 48 – Not Used
Digit 49 – Freeze Protection (Factory Installed)
X = None
2 = With freeze protection
Digit 50 – Evaporator Buffer Tank
X = No Tank
1 = With Tank
Digit 51 – Evaporator Water Strainer
X = No strainer
A = Factory installed strainer
Digit 52 – Appearance Options
X = No appearance options
Digit 53 – Staged Auxiliary heater
X = Without
1 = With Auxiliary heater relays
Digit 54 – Starter type
A = Across the line starter/Direct in Line
B = Soft starter
Digit 55 – Annunciation Relay
X = None
A = With
Digit 56 – Fan type
1 = AC fan
2 = EC fan
3 = EC for HESP (Field speed setting)
Digit 57 – Night Noise Setback (NNSB)
X = Without
1 = With NNSB (With EC fans only)
Digit 58 – Not Used
Digit 59 – Hot Loop Hydraulic Module
X = Signal On/Off Pump
2 = Single Pump Standard Pressure
4 = Single Pump High Pressure
1 = Dual Pump standard pressure, alternate running
3 = Dual Pump high pressure, alternate running
5 = Dual Pump standard pressure, simultaneous running
6 = Dual Pump high pressure, simultaneous running
Digit 60 – Hot Loop Primary flow control
X = Without VFD
F = With VFD for manual flow adjustment
Digit 61 – Hot Loop water strainer
X = No Strainer
A = With Strainer factory installed
Digit 62 – Not Used
Digit 63 – Not Used
Digit 64 – Not Used
Digit 65 – Special
X = Standard catalog
S = Special Requirement
Unit model number description

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Sintesis Balance CMAF and is the answer not in the manual?

Trane Sintesis Balance CMAF Specifications

General IconGeneral
BrandTrane
ModelSintesis Balance CMAF
CategoryChiller
LanguageEnglish

Related product manuals