11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVX051A-GB
53
Controls/Tracer TD7 Operator Interface
Controls Overview
CMAF units use the following control/interface
components:
Symbio™ Controller
Tracer TD7 Operator Interface
Communication Interfaces
There are four connections on the Symbio™ that
support the communication interface. See CMAF User
Guide to locate the following ports: “Wiring and Ports
Description” section.
BACnet MS/TP and BACnet IP
MODBUS RTU (Slave) and Modbus TCP (Slave)
See User Guide for information on communication
interface.
Tracer TD7 Operator Interface
Operator Interface
Information is tailored to operators, service technicians
and owners. When operating a Multi-Pipe unit, there is
specific information you need on a day-to-day basis, like
setpoints, limits, diagnostic information, and reports.
Day-to-day operational information is presented at the
display. Logically organized groups of information-
Multi-Pipe unit mode of operation, active diagnostics,
settings and reports put information conveniently at your
fingertips.
Tracer™ TU
The TD7 operator interface allows for daily operation
tasks and set point changes. However to adequately
service Sintesis CMAF Multi-Pipe units, Tracer™TU
service tool is required (Non-Trane personnel,
contact your local Trane office for software purchase
information). Tracer™
TU adds a level of sophistication that improves service
technician effectiveness and minimizes unit downtime.
This portable PC-based service-tool software supports
service and maintenance tasks.
Tracer™ TU Set-Up
Using Tracer™ TU service tool, adjust the settings. Refer
to Tracer™ TU manual and Tracer Symbio™ 800 user
guide for instruction on settings.
CAUTION! To prevent compressor damage, do not
operate the unit until all refrigerant valves and oil-line
service valves are opened.
IMPORTANT! A clear sight glass alone does not mean
that the system is properly charged. Also check system
discharge superheat, approach temperature and unit
operating pressures.