UX360 Smart Thermostat
18-HD98D1-1B-EN 9
8. Configuration
Certain menu selections may or may not be present depending on other menu settings and equipment
installed.
8.1 General
8.2 Climate Control
Menu
Selection
Options Description
System
Name
Manual
keypad entry
Enter a custom name for the system.
Dealer Code
Manual
keypad entry
When the system is connected to Trane Home, a Dealer Code can be
entered to populate the dealer’s contact information and logo. The code
is the dealer’s registered phone number listed on ComfortSite. A dealer
can upload a logo by selecting Tech Support from the Home page of
ComfortSite, then select Dealer Logo Management and upload logo. File
size should not exceed 3MB.
Factory
System
Restore
Full Restore
Erases all user and installer settings and restores the system to factory
default settings.
Partial
Restore
HVAC configuration will be set to factory default values. Zoning
configuration, indoor sensor settings, and user settings will be retained.
After the partial restore, HVAC configuration may need to be reconfigured.
Sub Menu Menu Selection
Options [Default]
Description
General
System
Operation
Cooling Sensible Load
Value (Btu/h)
[0] Btu/h
Range of values is based on system
configuration.
Heating Sensible Load
Value (Btu/h)
[0] Btu/h
Range of values is based on system
configuration.
Aggressive Recovery
by Temp Error
Enabled/[Disabled]
Select whether to disable the
15-minute staging inhibit during
heating mode when Temp Error is
greater than 2°F.
Cannot be enabled when Heating
Aggressive Recovery by ODT is
enabled.
Heating Aggressive
Recovery by ODT
Enabled/[Disabled]
Select whether to require/[bypass]
outdoor temperature to fall below
the selected Heating Aggressive
Recovery Setting in order to disable
the 15-minute staging inhibit during
heating mode when Temp Error is
greater than 2°F.
Cannot be enabled when Heating
Aggressive Recovery by Temp Error
is enabled.
Outdoor temperature sensor must be
connected and enabled to allow this
setting to be selected.