Chapter 3 Termination board wiring
24 BMTK-SVN01D-EN
Figure 14. Tracker field wiring connections
24VAC
THERMISTOR
COMM
ALARM
RELAY
PRIORITY
SHUTDOWN
METER
INPUT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
24 Vac
Line voltage
Line voltage
Comm5
link
Comm5
link
Comm5 deviceComm5 device
Splice
2
1
3
5
4
4
AA
BB
AA
BB
Legend
Twisted pair, shielded wire
per Trane specifications
Shield termination
Earth ground
Contact points
Thermistor device per
Trane specifications
Transformer
Termination resistor
Shield ground
=
=
=
=
=
=
=
=
LOAD
Figure note
=
Figure Notes:
1 All customer wiring must be in accordance with national, state, and local electrical codes.
2 Trane recommends a dedicated transformer for 24 Vac power.
3 Alarm relay circuit must not exceed 24 Vac, 1 A.
4 Do not apply voltage to the priority shutdown inputs.
5 Example of Comm5 communication link wiring. See product-specific literature for Comm5 wire connection details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracker Version 12 and is the answer not in the manual?

Trane Tracker Version 12 Specifications

General IconGeneral
BrandTrane
ModelTracker Version 12
CategoryAir Conditioner
LanguageEnglish

Related product manuals