Pre-installation wiring notes
BMTK-SVN01D-EN 69
®
Pre-installation wiring notes
The wiring for the Tracker system will have been completed prior to
Tracker installation. All Tracker wiring conforms to the following
guidelines:
The Tracker controller receives 24 Vac from a dedicated power circuit.
If not, the Tracker controller may malfunction.
Each UCM receives 24 Vac from a dedicated power source. If not, the
UCM may malfunction.
Input wires and ac power wires are run in separate conduits or wire
bundles. If not, the Tracker controller may malfunction due to
induced electrical noise.
Comm5 cable and ac power wires are run in separate conduits or wire
bundles. If not, the Tracker controller may malfunction due to
induced electrical noise.
UCM communication cables do not run near lighting ballasts or other
transformers. If they do, the UCM may malfunction due to induced
electrical noise.