The measured level is below the specified value.
This error can be caused by:
• Low oil level
• Mal functioning sensor
• High value of Level Low limit
It can be solved by:
• Refill the tank with oil
• Decrease Level Low limit value
Pump control: Temperature.
The measured temperature is above or below the limit values.
This error can be caused by:
• Low oil temperature
• High oil temperature
• Sensor malfunction
It can be solved by:
• Change oil temperature
• Adjust temperature Low limit
• Adjust temperature High limit
Pump control: Motor safety relay
The motor protection relay is active
This error can be caused by:
• Motor safety relay has been activated
• Motor safety relay malfunction or disconnected